RCCB
P 015 Low Voltage Brief Catalogue -
NL1
1. General
1.1 Function Protect people against indirect contacts and additional protection against direct contacts. Protect installations against fire hazard due to insulation faults. Residual current circuit breakers are used in housing, tertiary sector and industry. 1.2 Detectable wave form AC class Tripping is ensured for slowly increasing sinusoidal AC residual currents. A class Tripping is ensured for sinusoidal AC residual currents and for pulsed DC residual currents, whether applied suddenly or increasing slowly. S, G/SI class Tripping is ensured not only for sinusoidal AC residual currents but also for pulsed DC residual currents whether applied suddenly or increasing slowly. S, G/SI type with filters against spurious tripping caused by harmonics and transient surges. 1.3 Tripping sensitivity 10mA - precision instrument leakage protection and bathroom use. 30mA - additional protection against direct contact. 100mA - co-ordinated with the earth system according to the formula IΔn < 50/R, to provide protection against indirect contacts; 300mA/500mA - protection against indirect contacts, as well as fire hazard. Tripping time Instantaneous It ensures instantaneous tripping (without time-delay). Short time delay It ensures any tripping at least 10ms. Selective It ensures total discrimination with a nonselective RCD placed downstream With the impact of 8/20us surge 3000A, this high immunity RCCB will still be in stable status.
NL1
NL1
2.Technical features
IEC/EN 62423 & IEC/EN 61008-1
Standard
IEC/EN 61008-1
AC, A
AC-G,A-G,A-SI
AC,A
F
Type (wave form of the earth leakage sensed)
63,80,100 AC-S,A-S
Rated current In Poles Rated voltage Ue
25, 40, 63
25, 40, 63
80,100
25,40,63
A
1P+N, 3P+N 230/400~240/415 0.01for1P+N 25A, 0.03, 0.1, 0.3, 0.5 0.03, 0.1, 0.3 0.03, 0.1, 0.3 0.1, 0.3
V
0.03, 0.1, 0.3
Rated sensitivity I△n Insulation voltage Ui Rated residual making and breaking capacity I△m Short-circuit current Inc=I△c SCPD fuse break time under I△n Rated frequency
V A
500 500 (In=25A/40A)
500 (In=25A/40A)
500 (In=25A/40A)
1000 (In=80A/100A) 1000(In=63A/80A/100A)
A
Electrical features
630 (In=63A)
630 (In=63A)
630 (In=63A)
6000/10000
10000
A A
10000
≤0.1(Normal type), 10ms~300ms(G type). 150ms~500ms(S type)
s Hz
6000 2 50/60
Rated impulse withstand voltage(1.2/50) Uimp Dielectric test voltage at ind. Freq. for 1 min Pollution degree
V
kV