▪ Rated short-circuit breaking capacity(Icu): 10000A ▪ Short-circuit breaking capacity(Ics): 7500A ▪ Rated impulse withstand voltage(Uimp): 4kV
Modular Din Rail Product
P 033 Low Voltage Brief Catalogue -
AX-X1 Auxiliary contacts 、 AL-X1 Alarm auxiliary contact
▪ Compliant standards: IEC 60947-5-1 ▪ Rated insulation voltage (Ui): 500V ▪ Utilization category:AC-12,DC-12 ▪ Rated operation current under different rated operation voltage: AC-12:240V/6A,415V/3A; DC-12:130V/1A,48V/2A,24V/6A ▪ Life time: 10000 times
AX-X1
SHT-X1 Shunt release
▪ Rated insulation voltage (Ui): 500V ▪ Utilization category:AC-12,DC-12 ▪ Rated operation current under different rated operation voltage: AC-12:400V/3A,230V/6A,48V/3A,24V/6A; DC-12:48V/3A,24V/6A ▪ Action characteristics: within the range of 70% ~ 110% of the rated control supply voltage ▪ Life time: 4000 times
SHT-X1
▪ Rated operation voltage Ue: AC 240V 50Hz (or 60Hz) ▪ Rated insulation voltage Ui: 500V. ▪ Overvoltage setting value Uvo: 280V ▪ Mechanical and electrical life: ≥4000 operation cycles OVT-X1 Overvoltage release
OVT-X1
Modular Din Rail Product
P-085
Low Voltage Brief Catalogue
UVT-X1 Under-voltage release
▪ Rated operation voltage Ue: AC 240V ▪ Rated insulation voltage Ui: 500V ▪ Under voltage setting value: (35%~70%)Ue ▪ Mechanical and electrical life: ≥4000 operation cycles
UVT-X1
OUVT-X1 Over/under voltage release
▪ Rated operation voltage Ue: AC 240V, 50Hz
Powered by FlippingBook