CHD130 Single Phase DIN-Rail Meterw
SPECIFICATIONS
Measurement
Relay
Compliance with IEC/STS standard Element: 1 phase 2 wire / 1 phase 3 wire Accuracy: Class 1.0/0.5 for active
Internal relay One or Two relays Relay will disconnected when meter tamper, overload, credit not enough
Voltage
Communications
Nominal voltage (Un): 110V, 120V, 220V, 230V, 240V Operating range: 0.4Un-1.2Un Power consumption: Voltage circuit ≤ 1W, 5VA Current circuit ≤ 2VA
Optical port: IEC62056-21 compliant Uplink: RS485 / PLC Downlink: PLC / Mbus / RF / Bluetooth
DLMS/COSEM communication protocol compliant Communication with CIU and DCU supported
Current
Event Logs (Optional)
5(60)A/5(80)A/5(100)A
Standard event, tamper event, control event, grid event Configurable event alarming system (LED and buzzer) Meter tamper state indication on CIU LCD and LED
Frequency
50Hz or 60Hz
Security
Real-time Clock
Compatibility STS 20 digits token transfer into meter through keypad or remote communication.
Accuracy within 0.5 seconds per day at 23° C
LCD Display
Environmental
Energy impulse output Alarm indication include tampering and relay state Energy reverse for postpaid mode Balance for prepaid mode
Dimensions and Weight Dimensions: 140mm×90mm×52mm Weight: 0.6 kg (Approx.) Operating range limit: -40° C to +75° C Storage range limit: -40° C to +85° C Relative humidity: ≤ 95%RH Ingress protection: IP54
Battery (Optional) Built-in battery Voltage: 3.6V nominal
Backup time: 10 years with power
Measured Values Total kWh
Instantaneous kW, Irms, Vrms Cumulative and credit energy
LCD INDICATION
METER DIMENSIONS
Units: mm
Units: mm
Add: No.560, Yueming Road, Binjiang District, Hangzhou, Zhejiang, China P.C: 310052 Tel: +86-571-56977777 Fax: +86-577-62919588 E-mail: chintmeter@chint.com Website:http://en.chintim.com/ Zhejiang CHINT Instrument & Meter Co., Ltd