CHINT Electricity Meters

CHS120 Single Phase Smart Meter

SPECIFICATIONS

Measurement Compliance with IEC and EN standard Connection type: 1P2W, 1P3W Accuracy: Class 1.0 for active, Class 2.0 for reactive

Time of Use

Up to 4 rates Up to 4 seasons each year Up to 4 week table Up to 8 day table Up to 8 Time intervals per day

Voltage

Nominal voltage (Un): 110V, 120V, 220V, 230V, 240V Operating range: 0.5Un ~ 1.3Un Power consumption: ≤ 2W, 10VA

Relay (Optional)

Relay for phase line and neutral line Up to 10000 operations

Current

Keypad (Optional)

Ib : 5/10A Imax: 60/80/100A

4 x 3 matrix keypad

Event Logs

Frequency

Standard event, tamper event, control event, grid event Configurable event alarming system

50Hz or 60Hz

Real-time Clock

Load Profile

Accuracy within 0.5 seconds per day at 23 ℃

Up to 4 channels Over 4800 records per channel

LCD Display

8 characters of 7 segment display Digital size: 5mm × 10mm LCD display available without main power With backlight

Communications

Optical port / RS485 Uplink: G3-PLC/GPRS/4G/Wi-SUN module Downlink: Mbus/RF Protocol: DLMS/COSEM

Battery (Optional) Battery easy replaced Voltage: 3.6V

Environmental

Operating range limit: -40° C to +75° C Storage range limit: -40° C to +85° C Relative humidity: ≤ 95%RH Ingress protection: IP54

Backup time: 10 years with power

Measured Values Import/Export/Absolute/Algebraic kWh Import/Export/ kvarh Instantaneous kW, kvar, kVA, Irms, Vrms, Frequency, Power factor

Dimensions and Weight

Dimensions: 210mm × 130mm × 65mm Weight: 0.7 kg (Approx.)

Maximum Demand Maximum demand: kW, kvar Intervals programmable from 5 to 60 minutes

LCD INDICATION

METER DIMENSIONS

Units: mm

Units: mm

Add: No.560, Yueming Road, Binjiang District, Hangzhou, Zhejiang, China P.C: 310052 Tel: +86-571-56977777 Fax: +86-577-62919588 E-mail: chintmeter@chint.com Website:http://en.chintim.com/ Zhejiang CHINT Instrument & Meter Co., Ltd