SPECIFICATIONS
Measurement
Maximum Demand Maximum demand: kW, kvar Intervals programmable from 5 to 60 minutes
Compliance with IEC standard Connection type:1P2W Accuracy: Class 1.0 for active, Class 2.0 for reactive
Time of Use
Voltage
4 rates (default) Up to 4 seasons each year Up to 4 week table Up to 4 day table Up to 24 Time intervals per day
Nominal voltage (Un): 220V, 230V, 240V Operating range: 0.4Un ~ 1.2Un Power consumption: ≤2W, 10VA
Current
Relay (Optional)
Ib : 5A Imax: 40/60A
Relay for phase line (default) Up to 10000 operations
Frequency
Event Logs
50Hz or 60Hz
Tampering detection, power quality and general events Configurable event alarming system
Real-time Clock
Accuracy within 0.5 seconds per day at 23°C
Load Profile
LCD Display
2 channels (default) Up to 5760 records per channel
8 characters of 7 segment display Digital size: 4.5mm × 9mm LCD display available without main power
Communications
Optical port Uplink: 2G/4G/G3-PLC/Wi-SUN module Protocol: DLMS/COSEM
Battery (Optional) Battery easy replaced Button cell
Environmental
Operating range limit: -25°C to +70°C Storage range limit: -25°C to +80°C Relative humidity: ≤ 95%RH Ingress protection: IP56
Measured Values Import/Export/Absolute/Algebraic kWh Import/Export/ kvarh Instantaneous kW, kvar, kVA, Irms, Vrms, Frequency, Power factor
Dimensions and Weight
Dimensions: 137.5mm × 160mm × 80mm Weight: ≤1Kg
LCD INDICATION
METER DIMENSIONS
Units: mm
Units: mm