CHINT Electricity Meters

DDSY666 Single Phase DIN-Rail Meter

SPECIFICATIONS

Relay

Measurement

One relay Up to 10000 operations

Compliance with STS standard Connection type: 1P2W Accuracy: Class 1.0 for active

Communications

Voltage

Optical port PLC/M-Bus (optional) communication with IHD Protocol: IEC62056-21 Communication with DCU through PLC (optional)

Nominal voltage (Un): 110V, 120V, 220V, 230V, 240V Operating range: 0.7Un ~ 1.2Un Power consumption: ≤ 1.5W, 5VA

Current

Event Logs (Optional)

5(60)A/5(80)A/5(100)A

Standard event, tamper event, control event, grid event Configurable event alarming system (LED and buzzer) Meter tamper state indication on IHD LCD and LED

Frequency

50Hz or 60Hz

Security

Real-time Clock

Compatibility STS 20 digits token transfer

Accuracy within 0.5 seconds per day at 23° C

Environmental

LCD Display

Operating range limit: -40° C to +75° C Storage range limit: -40° C to +85° C Relative humidity: ≤ 95%RH Ingress protection: IP54

Number of flashes per kWh Communication indication Relay indication

Battery (Optional) Built-in Battery Voltage: 3.6V nominal

Dimensions and Weight

Dimensions: 143mm ×103mm × 55.4mm Weight: 0.6 kg (Approx.)

Backup time: 15 years with power

Measured Values Total kWh

Instantaneous kW, Irms, Vrms Cumulative and credit energy

METER DIMENSIONS

Units: mm

Add: No.560, Yueming Road, Binjiang District, Hangzhou, Zhejiang, China P.C: 310052 Tel: +86-571-56977777 Fax: +86-577-62919588 E-mail: chintmeter@chint.com Website:http://en.chintim.com/ Zhejiang CHINT Instrument & Meter Co., Ltd