EnergiX-P40 catalogue
3.0
Product introduction
IBCPM Characteristics
Communication / Interface
RS-485: Modbus-RTU (Default) / Optional Modbus TCP
Physical interface
RS-485
Communication speed
Up to 38.4 kbps
Communication protocol
Modbus-RTU / Optional Modbus TCP
Measurement Parameters
Power Quality Analysis
Wave Sampling
128 samples/cycle
Harmonic
31st Harmonic (Main Circuits)
Alarm setting
Setpoint alarm and record
Voltage, Current, Active power, Reactive Power, Apparent Power, Power Factor, Frequency, THD
Real-time Data
Measurement Channel
2 main circuits and 24 channels sub circuits
Memory Record
Memory
2MB
/RDGVHWWLQJIURPSUHYLRXVVDYHGnOHRUVHW Rated range 50 - 600V (L-L) according to needs.
Setting
Accuracy
Voltage/ Current
±0.2%
Re-,Active/Apparent power
±0.2%
Active Energy
±0.5%
Reactive Energy
±0.5%
Power Factor
±0.5%
Frequency
±0.1%
THD
1%
Unbalance
±0.5%