CHINT EnergiX-P40 Brochure

EnergiX-P40 catalogue

3.0

Product introduction

IBCPM Characteristics

Communication / Interface

RS-485: Modbus-RTU (Default) / Optional Modbus TCP

Physical interface

RS-485

Communication speed

Up to 38.4 kbps

Communication protocol

Modbus-RTU / Optional Modbus TCP

Measurement Parameters

Power Quality Analysis

Wave Sampling

128 samples/cycle

Harmonic

31st Harmonic (Main Circuits)

Alarm setting

Setpoint alarm and record

Voltage, Current, Active power, Reactive Power, Apparent Power, Power Factor, Frequency, THD

Real-time Data

Measurement Channel

2 main circuits and 24 channels sub circuits

Memory Record

Memory

2MB

/RDGVHWWLQJIURPSUHYLRXVVDYHGnOHRUVHW Rated range 50 - 600V (L-L) according to needs.

Setting

Accuracy

Voltage/ Current

±0.2%

Re-,Active/Apparent power

±0.2%

Active Energy

±0.5%

Reactive Energy

±0.5%

Power Factor

±0.5%

Frequency

±0.1%

THD

1%

Unbalance

±0.5%

CHINT | 12