NIPower DC7000 Brochure
Empowering the Data Center for Tomorrow
NIPower DC7000 Fusion Power Module
NIPower DC7000 Fusion Power Module
UPS
SVG
APF
800
2,100
1,200
700
850
550
MV
Transformer
Incoming
Compensation
UPS
Input(Output)
NIPower Fusion is an integrated prefabricated skid power module specifically designed for critical power systems such as data centers. It features a fully customized design, factory prefabrication, and modular construction. By integrating the electrical equipment, the modules enable large-scale production, in-factory commissioning, and modular delivery. This reduces the need for extensive on-site installation, wiring, and commissioning, ensuring higher eciency and workmanship.
The modules can be configured to include medium voltage switchgears, transformers, low-voltage switchgears, UPS, and outgoing feeder switchgears. With a unified structure, the modules are factory-assembled and transported as a complete system.
UPS
UPS
UPS
850
550
850
550
850
550
800
600 600
Feeder
Feeder
UPS
Input(Output)
UPS
Input(Output)
UPS
Input(Output)
Maintenance Bypass
12,400
Key Features
Safe, reliable & controllable NIPower DC7000 Fusion Power Module includes a medium voltage cabinet, dry-type transformer, low voltage cabinet, electrical components, monitoring system, and integrated assembly, all independently developed and produced by CHINT. These self-controlled products ensure the safe and reliable operation of the IT and power equipment.
Medium Voltage Switchgear Certification: Passed Seismic Resistance, Moisture, Pollution, High Altitude, Internal arc, and EMC tests. Performance: Mechanical life up to 50,000 cycles, electrical life up to 70 cycles.
Low-voltage Switchgear Certification: Certified with
Dry-type Transformer Certification: Certified with IEC 60076-11 Material: Electrical steel strip/amorphous alloy dry-type transformer Eciency: 99.36%
IEC 61439-2 and compliant with Seismic Resistance, Salt Spray, High Altitude, Internal Arc, and EMC tests. Adaptability: Independent design and development, suitable for a variety of low voltage switchgear types Combination: The distribution busbar for the molded case feeder is 2500A
KYN28 - 12/24
SCB(18)/SCBH(19)
MNS/NGC8
Electrical Components
Performance: Icu=Ics=Icw Parameters: 65kA to 135kA Eciency: “Dual Core” Smart control unit/ Tri-color LCD display Safety: Full selective protection and Energy reduction maintenance setting (ERMS)
NA8 & Ex9 Series Circuit breaker
NIPower DC7000 Fusion Power Module
NIPower DC7000 Fusion Power Module undergoes the mechanical simulation, the thermal dynamic simulation, and the dynamic and thermal stability calculations. Mechanical simulation ensures the reliability of the switchear and its base, the thermal dynamic simulation ensures the rationality of the heat dissipation design, while the dynamic and thermal stability calculations ensure the reliability of components and conductors.
Thermal Dynamic Simulation
Dynamic & Thermal Stability Calculation
Mechanical Simulation
CHINT DATA CENTER NIPOWER
ELECTRICAL CALCULATION
1. Short Circuit Calculations 1.1 Design Parameters 1.2 Short Circuit Calculations
4. Temperature Rise Calculation 4.1 Main Busbar Temperaure Rise Calculation
Smart Solutions System The independent monitoring system achieves full-chain visualization management and predictive maintenance by collecting all electrical parameters, the temperature of key connection points, and switch status. Additionally, the monitoring software can be custom designed or upgraded according to customer’s requirements.
No. Components of the Products 1 2 1 Technical Indicators Rated Operating Voltage (Ue) 400V Rated Insulation Voltage (Ui) 2
Dry-type Transformer • Capacity: 800 - 3,150kVA. • Connection type: Dyn 11. • Voltage ratio: 6,6.3,6.6,10,10.5,11,20,22,24,35~38.5 / 0.4 kV.
• Temperature rise: When operating at full nominal capacity, the average tempera- ture rise should not exceed 100K (F-class insulation). For H-class insulation, the average temperature rise should not exceed 125K. • Certification: Certified with IEC 60076-11. • Overload capacity: At rated kVA capacity, it can run continuously for 24 hours and can operate at 100% full load for a long time. • Partial discharge level: After applying a pre-stress voltage of 1.8 Ur between phases for 30 seconds, reduce the voltage to 1.3 Ur and continue the test for 3 minutes, with the discharge amount less than 10 pC (Ur is the rated voltage). • Service life: The transformer has a service life of no less than 30 years. Under the normal usage condition, the transformer will not suer any damage due to temperature changes during its service life.
Low-voltage Switchgear The switchgear is a modular, flexible solution for ecient power distribution. Allowing quick component removal for maintenance without system shutdown, ensuring safety and minimal downtime. Designed with compact size, the switchgear complies with IEC 61439 and relevant standards for seismic, internal arc, EMC and more.
Product Specifications
1,000V (Incoming Cabinet, Feeder Cubicle); 800V (Control Cubicle)
3 Rated Frequency (fn) 4 Rated Current of Main Busbar (InA) 5 Rated Short-time Withstand Current of Main Busbar (Icw)
50Hz / 60Hz 6,300A - 1,600A 85kA
6
Rated Short-time Withstand Current of Control Cubicle Busbar (lcw)
65kA / 1s
7 Enclose Protection Level
IP3X, IP4X (*Enclosure protection level customizable upon request)
Green Power
NIPower DC7000 Fusion Power Module
3
UPS • All Module Hot-swappable Design • Power Factor 1 (kVA=kW) • High Eciency 97% •System Parallel up to 8 units • Fault Trace Management • Most compact 100KW module 3U
It is a high density design modular UPS with the high eciency up to 97%.100 module with 3U design and can reach a total 600kAV into a single cabinet. Small footprint suitable for dierent applications. The hot-swappable module design, allow the fast plug and play maintenance. At the same time,It also compatiable with the lithium-ion battery. High density, High eciency, hot-swappable and redundant design UPS oer high availability and high performance.
User-friendly Interface
High Reliability
More Options
Intelligent Management
Asia Pacific
APAC HQ | Singapore CHINT Global International Pte Ltd Address: 8 Kallang Avenue, #04-06/09 Aperia Office Tower 1, Singapore 339509 Tel: +65 6329 3110 Fax: +65 6329 3159 Email: Sales.APAC@CHINT.com Web: www.CHINTGlobal.com
Australia CHINT Australia Pty Ltd Address: 3/20 Cliff Street, Milsons Point, New South Wales 2061 Tel: 1800 270 870 Email: info.australia@CHINT.com Web: www.CHINTGlobal.com.au Cambodia CHINT (Cambodia) Power Equipment Co., Ltd Address: #39, Street 337, Borey Sunway City, Village 1, Sangkat Boeng Kok 2, Khan Tuol Kork, Phnom Penh, Cambodia Tel: +855 23 231 077 Email: info-cambodia@CHINTGlobal.com Web: www.CHINTGlobal.com SchneiTec CHINT Co., Ltd Address: Ansor Kdam Village, Sna Ansa Commune, Krakor District, Pursat Province, Cambodia Tel: +855 09 5353 268 Email: Liubin@SchneiTec-CHINT.com.kh / Info@SchneiTec-CHINT.com.kh Web: www.SchneiTec-CHINT.com.kh
Indonesia PT. CHINT Indonesia Address: Gold Coast Office, Eiffel Tower, Jl. Pantai Indah Kapuk,
RT.7/RW.2, Kamal Muara, Kec. Penjaringan, Jkt Utara, Daerah Khusus Ibukota Jakarta 14470, Indonesia
Tel:
+62 21 5436 3000
Email:
Sales@CHINT-Indonesia.com www.CHINT-Indonesia.com
Web:
Malaysia Alpha Automation (Selangor) Sdn. Bhd. Address: No. 11, Temasya 18, Jalan Pelukis U1/46B, Seksyen U1, 40150 Shah Alam, Selangor, Malaysia Tel: +603-5569 7787 Fax: +603-5569 9295 Email: CHINTMalaysia@AlphaSel.com Web: www.AlphaSel.com Philippines CHINT Electric Co., Ltd Address: Unit 201, Taipan Place, F. Ortigas Jr. Road, Ortigas Center, Pasig City, Metro Manila, Philippines Tel: +63 (02) 836 53068 Email: chintph@CHINTGlobal.com Web: www.CHINTGlobal.com Thailand CHINT Electric Thailand Co., Ltd. Address: 66 Tower, No. 2556, Sukhumvit Road, Bang Na District, Bangkok 10260, Thailand Tel: +86 17851901128 Email: jzliang@chint.com Web: www.CHINTGlobal.com
India CHINT India Energy Solution Private Limited Address: Noida
Discovery Tower Plot No A-17, Ground Floor, Sector – 62 Noida – 201309 Bangalore Building No. 35, First Floor, 28th Cross Road, 9th Main, Industrial Layout, Banashankari 2nd Stage, Bangalore, Karnataka – 560070
Tel:
+91 1202 9750 57
Email:
Marketing@CHINT.co.in
Vietnam CHINT Vietnam Holding Co., Ltd Address: Ho Chi Minh City
Web:
www.CHINT.co.in
Level 3 The CREST Residence, No. 1 - No. 15, Tran Bach Dang Street, An Khanh Ward, Ho Chi Minh City, Vietnam Hanoi Level 23, Lotte Center Hanoi, 54 Lieu Giai, District Ba Dinh, Hanoi, Vietnam
Tel:
+84 0283 8270 015
Email:
Marketing.VN@CHINTGlobal.com
Web:
www.CHINTGlobal.vn
CHINT GLOBAL INTERNATIONAL PTE LTD 8 Kallang Avenue, #04-06/09, Aperia Tower 1, Singapore 339509
Tel Email Web
: : :
+65 6329 3110 Sales.APAC@CHINT.com www.CHINTGlobal.com
AP001817-102024
Printed by CHINT Global. No part of this brochure shall be used or reproduced in any form without written permission by CHINT Global. CHINT is the only publisher and editor for the content. !