CHINT NXA Brochure

TECHNICAL PARAMETERS NXA Air Circuit Breaker

Frame Size

1600A

Rated current (A)

400 630 800 1000 1250 1600

Rated current of the fourth pole (A)

400 630 800 1000 1250 1600

Number of poles

3 and 4

Type of the Circuit Breaker

N

S

H

Rated ultimate short circuit breaking capacity (kA rms) VAC 50/60Hz Rated service breaking capacity (kA rms) VAC 50/60Hz

Icu

380/400/415V 440/525/690V 380/400/415V 440/525/690V 380/400/415V 440/525/690V 380/400/415V 440/525/690V 380/400/415V 440/525/690V

50 30 42 30

42 36 42 36 42 36 25 -

50 36 50 36 42 36 25 -

Ics

Utilization category

B

Rated short-time withstand current (kA rms) VAC 50/60Hz

Icw 1s

42 30 20 -

Icw 3s

Rated making capacity (kA) VAC 50/60Hz

Icm

105 63

88.2 75.6

105 75.6

Making current tripping protection function (MCR kA ms)

10

16

16

Breaking time (ms)

32

Closing time (ms)

70

Installation, Connection and Service Life Service life C/O cycle

Mechanical With

30000

maintenance Without maintenance Without maintenance

15000

Electrical

8000

Connection

Horizontal

Dimensions (Width x Depth x Height) in mm

Fixed type 3P

254 x 243.5 x 318.5

4P

354 x 243.5 x 318.5

Draw-out type

3P

308 x 331.5 x 351

4P

378 x 331.5 x 351