Data Center Solutions Leaflet
Low-voltage Brief Catalogue
LOW-VOLTAGE
ABOUT CHINT
Zhejiang CHINT Electrics Co., Ltd. is a wholly owned subsidiary of CHINT Group. Cultivating R&D, manufacturing and sales of low-voltage products, we provide system solutions for building, power supply, hoisting, HVAC, telecommunication and other industrial customers. For nearly 40 years since its founding, CHINT Electrics has provided reliable products and services to over 140 countries and regions. Today, CHINT has grown to be one of the world’s renowned low-voltage brands.
CHINT Honors 2022 • “AAAAA” standardized good behavior certificate • “Global Partnership” and “Countries along the Belt and Road” in the “2021 Best Practices for Realizing the Sustainable Development Goals” • CSR Impact Leading Enterprise 2021 • No. 1 in “China’s Top 100 Private Enterprises with Social Responsibility” in 2021 • For 8 consecutive years, CHINT has won the sales champion of Tmall double 11 in electrical and hardware industry • No. 92 in “2021 China’s Top 500 Private Enterprises” • No. 244 in “2021 Top 500 Chinese Enterprises” • The intelligent manufacturing factory of low-voltage electrical appliances was selected as the national “2021 Intelligent Manufacturing Demonstration Factory”
2020 • CHINT was selected in the 2020 Zhejiang Province “Future Factory” recognized list, and was rated as the leading “ Leading Goose Factory” • The key inverter technology of CHINT won the second prize of China Electric Power Science and Technology • CHINT Astrometry was selected as the smart PV demonstration enterprise list of the Ministry of Industry and Information Technology and won the honor of “Influential PV cell/module brand”, “Influential PV EPC / End User”, “Influential PV power station operation and maintenance brand” 2019 • National Green Factory • National Industrial Design Center of the MIIT • Global Top 20 PV Enterprise • China’s Top 10 Successful PV Enterprise • Top 100 Innovative Enterprises in Zhejiang Province • Technology innovation system was awarded the 2018 Science and Technology Progress Award in Zhejiang
CHINT A global leading smart energy solutions provider
CHINT was established 40 years ago in 1984 and built from the capital of approximately 8,000 US dollars. With our rapid development these years, CHINT has become the world’s leading intelligent energy solutions provider for the whole industrial chain with the most complete product ranges. In 2023, our annual sales revenue surpassed 22.1 billion US dollars, and our total assets exceeded 25 billion US dollars. Over two decades of global expansion, our business network covers more than 140 countries and regions worldwide in business industries of low-voltage electric, power transmission and distribution, smart technology, energy instruments and meters, green energy, solar and more. CHINT has more than 50,000 employees worldwide, creating more than 200,000 jobs in the industrial chains. As the market localization progresses steadily, CHINT Global further establishes its supply chain through business integration and industrial upgrade. Optimizing the service system and project financing, providing innovatively integrated technical services for the global energy market, and a flexible working business model.energy, intelligent manufacturing and digital technology, CHINT has adopted “One Cloud & Two Nets” as the business strategy, takes “CHINT Cloud” as the carrier of intelligent technology and data application, and takes the lead in building the energy Internet of things (EloT) and industrial Internet of things platforms (loT). Focusing on the energy system of supply, storage, transmission, distribution and consumption, CHINT has core businesses of clean energy, energy distribution, big data and energy value-added services. Furthermore, CHINT’s pillar businesses include photovoltaic equipment, energy storage, power transmission & distribution, low-voltage apparatuses, intelligent terminals, software development and control auto- mation. By developing into a platform-based enterprise, CHINT provides a package of energy solutions for public institutions, industrial & commercial users and end-users, by building a regional smart energy operation ecosphere. Main Businesses
Qualification Certificates The products have been accredited through China Compulsory Certification (CCC) as well as UL of US, CE of EU, VDE and TÜV of Germany, KEMA of Netherlands, RCM of Australia, RCC of South Africa and other international product certifications.
Clean Energy
Low-voltage Apparatus
Smart Home
Power Transmission and Distribution
Instrumentation and Apparatus
Intelligent Building
Intelligent Manufacturing
Industry Automation
Smart Heating
Smart Water
Home Electrical Apparatus
Energy Efficiency Management
GLOBAL FOOTPRINT
R&D, QUALITY, SALES, LOGISTICS
Main Advantages Global R&D System
Canada
Poland
CHINT has established national R&D centers in North America, Europe, Asia Pacific, North Africa and other areas. We have explored the mode of Industry-University Research Institute Collaboration and Integration together with the universities and research institutions worldwide so as to integrate the global innovation resources and promote corporate R&D innovation and talent cultivation.
UK
Netherland
Kazakhstan
Czech Republic
France
Romania
USA
Italy
Turkey
South Korea
Spain
Mexico
Shanghai
Egyptt
The average annual R&D investment accounts for 4-12% of the revenue
U.A.E
Hongkong
24 Research Institutes
Over 8000 patents in total
India
Saudi Arabiat
Vietnam
Malaysia
Nigeria
Singapore
Global Certification The products have passed the standards and specifications in various regions around the world and obtained numerous international certifications.
Indonesia
Kenyat
Peru
Brazil
4 6 20+
18
Manufacturing Bases: China (Wenzhou, Hangzhou, Shanghai, Jiaxing, Xianyang, Jinan, Yancheng, Shenyang, Wuhan), Thailand, Singapore, Vietnam, Malaysia, Egypt, Uganda, Algeria, Cambodia and Saudi Arabia Countries and Regions of Business Coverage
National R&D Centers: North America, Europe, Asia Pacific, North Africa
International Marketing Territories: Asia Pacific, Western Asia and Africa, Europe, Latin America, North America, China
140+ 2300+
International Logistics Centers
Global Distributors
Global Capacity Layout The industrial manufacturing bases are mainly located in China (Wenzhou, Hangzhou, Shanghai, Jiaxiang, Xianyang and Yancheng). Additionally, CHINT has set up factories in China (Jinan, Shenyang, Wuhan), Thailand, Singapore, Vietnam, Malaysia, Egypt, Uganda, Algeria, Cambodia and Saudi Arabia.
Integrated Vertical R&D By gathering the global industry elites to provide safe and stable energy-saving green and advanced electric products.
Great Quality System Ensuring flaw-fraw-free and trouble-free products, the multi-dimensional and multi- level control is conducted through procurement,inspection, quality control and certification.
One-stop Service CHINT’s concept is that it is not difficult to fulfill a high quality logistics distribution at one time, while it is difficult to stay as accurate and prompt as the first time. High-efficiency and high -precision accuracy are our requirements.
48-Hour Response Providing end-to-end one-stop services for customers with feedback, business consulting and technical support by solving problems immediately and to include any possible problems in advance .
Wenzhou
Hangzhou
Shanghai
Xianyang
Jiaxing
Jinan
Yancheng
Singapore
Vietnam
Wuhan
At least 5% of revenue is invested in research and development
5%
Malaysia
Egypt
Algeria
Cambodia
Thailand
Low-voltage Brief Catalogue
Low-voltage Brief Catalogue
Modular DIN Rail Product
Relay
P-001
P-081
MCCB
LV Capacitor
P-047
P-099
ACB
Transformer
P-057
P-105
Motor Control & Protection
P-063
P-113
Switch Disconnector
Control & Signal
P-071
P-119
Machines Tool Apparatus
Inverter & Soft-starter
P-077
Modular Din Rail Products Perfect reliable choice
Modular DIN Rail Products
Modular DIN Rail Products
MCB
RCCB
NB1-63H In: 1~63A 10000A
NB1-63G In: 1~63A
NL1 A,AC,F type In=20~100A
NL210 B type In=25~63A
NXL-63 In=16~63A
NB1-63 In: 1~63A Icn=6000A
In: 1~63A Icn=3000A, 4500A
Page P-001
Page P-001
Page P-002
Page P-003
Page P-015
Page P-016
Page P-017
RCBO
NXB-40 In=6~40A Icu=4500A
NXB-63 In=1~63A Icn=6000A
NXB-63H In=1~63A Icn=10000A
NBH8 In: 1~40A Icn=4500A, 6000A
NB310L Magnetic type
NB2LE Electronic type
NB1L-40/63 Magnetic type
NB1L Magnetic type
Page P-004
Page P-005
Page P-005
Page P-005
Page P-018
Page P-019
Page P-020
Page P-021
NB8-63H In=1~63A Icn=10000A
NXB-80 In=80A Icn=6000A
NXB-125G In=63A,80A, 100A,125A Icn=10000A
NB8-63 In=1~63A Icn=6000A
NB3LEG-40 Electronic type
NB3LE Electronic type
NB3LEU Electronic type
NB4LE Electronic type
Page P-006
Page P-006
Page P-007
Page P-008
Page P-022
Page P-023
Page P-024
Page P-025
NB8-63M In=1~63A Icu=10000A
NB8-40J In=1~40A Icn=6000A
NBH8LE Electronic type
NB8LE-63M In=6~63A Icu=10000A
DZ158LE Electronic type
NXBLE-32 In=6~32A Icu=6000A
Page P-009
Page P-010
Page P-026
Page P-027
Page P-028
Page P-029
DC MCB
NB1-63DC In: 1~63A Icu=6000A
NXBLE-63Y In=6~63A Icu=4500A
NXBLE-125 In=60~125A Icu=7500A
NXBLE-63 In=6~63A Icu=6000A
CB-125 In=63~125A Icn=20KA
NXBLE-40 I n=6~40A Icu=4500A
CB-60 In=1~63A Icn=6KA
Page P-029
Page P-029
Page P-030
Page P-030
Page P-011
Page P-012
Page P-012
MCCB
AFDD
DZ158 In: 63A, 80A, 100A, 125A Icu=6kA, 10kA
NXB-125 In=63~125A Icu=10000A
NB3LE-AFD Electronic type
NB4LE-AFD Electronic type
Page P-013
Page P-014
Page P-031
Page P-032
Modular DIN Rail Products
Modular DIN Rail Products
Accessories for MCB, RCBO
Change-over Switch
XF9 Auxiliary contact
XF9J Alarm auxiliary contact For NB1,NBHB, NB1L,NBH8LE
S9 Shunt release
V9 Under-voltage release For NB1,NBHB, NB1L,NBH8LE
NZK1
NZK2
For NB1,NBHB, NB1L,NBH8LE
For NB1,NBHB, NB1L,NBH8LE
Page P-033
Page P-033
Page P-033
Page P-033
Page P-039
Page P-039
Surge Arrester
AX-1 Auxiliary contact
AX-5 Auxiliary contact
OUVR-1 Self-recovery Protector
OUVR-2 Self-recovery Protector
NU6- Ⅲ
NU6- Ⅱ G
NXUI+II
For DZ158, DZ158LE
For NL1
Page P-034
Page P-034
Page P-034
Page P-034
Page P-040
Page P-040
Page P-041
AX-X1 Auxiliary contacts
SHT-X1 Shunt release
OVT-X1 Overvoltage release For NXB, NXBLE series Page P-035
UVT-X1 Under-voltage release For NXB, NXBLE series Page P-035
Pushbutton & Indicator
Page P-035 For NXB, NXBLE series
Page P-035 For NXB, NXBLE series
NP9 Pushbutton
ND9 Indicator light
OVT-X3 Over-voltage release
OUVT-X1 Over/under voltage release For NXB, NXBLE series Page P-036
AX-X3 Auxiliary contacts
SHT-X3 Shunt release
Page P-042
Page P-042
For NXB-125, NXBLE-125 series
For NXB-125, NXBLE-125 series
Page P-036 For NXB-125, NXBLE-125
Page P-036
Page P-036
Consumer Unit
UVT-X3 Under-voltage release
OUVT-X3 Over/under voltage release For NXB-125, NXBLE-125 series
NX8
NX2
NXW1
For NXB-125, NXBLE-125 series
Page P-037
Page P-037
Page P-043
Page P-043
Page P-043
Switch Disconnector
Wall Mounting Enclosure
Busbar
NH2 In=32A, 63A, 100A, 125A
NH4 In=32A, 40A,63A, 80A,100A, 125A; Page P-038
NXW5
CBB-2 Busbar
Page P-037
Page P-044
Page P-045
NB310L Residual Current Operated Circuit Breaker with Over-current Protection (Magnetic)
003
004
1. General
NBH8 � Protection against risk of fire � Protection against risk of electric shock
NB1-63G
1. General � Protection against overload � Protection against short circuit � Contact position indicator • Short circuit protection • Overload protection • Switch • Isolation • 1P+N in one module • Contact position indicator
1. General
• Short circuit protection • Overload protection • Switch • Isolation • Various wiring solutions: U-type/pin-type/Comb-type Busbar/Cable
2. Technical features
NB310L (2P)
IEC/EN 61009-1
Standard Type (wave form of the earth leakage sensed)
A, AC
A
3PN
2P
Poles
Thermo-magnetic release characteristic
B, C
6-40 3P+N 400
A
6-32 2P
Rated current In Poles
2. Technical features
2. Technical features
NB1-63G
NBH8
Standard Rated voltage Ue Rated sensitivity I △ n Rated short-circuit capacity lcn Break time under I △ n Electrical life Mechanical life Rated current In Poles Rated voltage Ue
230/240
A V A s
0.03
IEC/EN 60898-1
Standard
IEC/EN 60898-1
6,000 ≤ 0.1
A 1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63
Rated current In
A 1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63
1P, 2P, 3P, 4P 230/400 2,000 2,000
Poles
1P, 2P, 3P, 4P
V
10000
Thermo-magnetic release characteristic
B, C
Rated voltage Ue
V
230/400
On DIN rail EN 60715 (35mm) by means of fast clip device From top and bottom
Mounting
Rated frequency
Hz 50/60 A 6000
Rated frequency
Hz 50/60
Rated breaking capacity
Connection
Rated breaking capacity
A 6000
Rated impulse withstand voltage (1.2/50) Uimp
V 4000
Rated impulse withstand voltage (1.2/50) Uimp Thermo-magnetic release characteristic
V 4000
Electrical life
4,000
3. Curve
NB310L (3PN)
Mechanical life
20,000
B, C curve
B, C
Mounting
On DIN rail EN 60715 (35mm) by means of fast clip device
t(s) 10000 5000 1h 2000 1000
Electrical life
4,000
Terminal connection type
Cable/Pin-type busbar
Mechanical life
20,000
Auxiliary contact
Yes Yes Yes Yes
Shunt release
Mounting
On DIN rail EN 60715 (35mm) by means of fast clip device
B
500 200 100
Under voltage release
Connection
From top and bottom
Alarm contant
50 20 10
C
5 2 1
3. Curve
3. Curve
0.5 0.2 0.1
B, C, curve
B, C, curve
0.05 0.02 0.01
t(s) 10000 5000 1h 2000 1000
10000 t(s)
0.005 0.002 0.001
2000 5000 500 1000
0.5 1
2 34 5 7 10 20 30 5070100 200 I/In
B
B
500 200 100
50 200 100
50 20
20 10
C
10 5 2 1
5
C
2
1
0.5
0.5 0.2
0.2
0.1
0.1 0.05 0.02 0.01
0.005 0.05 0.02 0.01 0.002 0.001
0.005 0.002 0.001
2 34 5 71 02 0 30 5070100 200 I/In
0.51
I/In 100 200
1
0.5
77 10
20
30 50 0
2 3 4 5
005
006
NXB-40
NXB-80
• Compliant standards: IEC60898-1 • Rated current: 6A, 10A, 16A, 20A, 25A, 32A, 40A
• Compliant standards: IEC60898-1 • Rated current: 80A • Rated voltage: 240/415V • Frequency: 50/60Hz • Electromagnetic release type: B, C, D
• Rated voltage: 240 • Frequency: 50/60Hz • Electromagnetic release type: C, D • Number of poles: 1P+N
• Number of poles: 1P, 1P+N, 2P • Mechanical life: 20000 cycles • Electrical life: 10000 cycles • Rated impulse withstand voltage(Uimp): 4kV • Protection of circuits against short-circuit currents, overload currents, switch, isolation
• Mechanical life: 20000 cycles • Electrical life: 10000 cycles • Rated short-circuit breaking capacity(Icu): 4500A • Short-circuit breaking capacity(Ics): 4500A • Rated impulse withstand voltage(Uimp): 4kV
NXB-40
NXB-80
NXB-63
NXB-125G
• Compliant standards: IEC60898-1 • Rated current: 1A,2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A • Rated voltage: 240/415V • Frequency: 50/60Hz • Electromagnetic release type: B, C, D • Number of poles: 1P, 1P+N, 2P, 3P, 3P+N, 4P
• Compliant standards: IEC/EN60898-1 • Rated current: 63A, 80A, 100A(1P, 2P, 3P, 4P), 125A (1P, 2P) • Rated voltage: 230V ~ (1P), 400V~ (2P, 3P, 4P) • Frequency: 50/60Hz • Electromagnetic release type: B, C, D • Number of poles: 1P, 2P, 3P, 4P • Mechanical life: 20000 cycles • Electrical life: 6000 cycles (In ≤ 100A); 4000 cycles (In > 100A) • Rated short-circuit breaking capacity(Icn): 10kA
• Mechanical life: 20000 cycles • Electrical life: 10000 cycles • Rated short-circuit breaking capacity(Icu): 6000A
NXB-63
NXB-125G
• Short-circuit breaking capacity(Ics): 6000A • Rated impulse withstand voltage(Uimp): 4kV • Protection of circuits against short-circuit currents, overload currents, switch, isolation
• Short-circuit breaking capacity(Ics): 7.5kA • Rated impulse withstand voltage(Uimp): 4kV
NXB-63H
• Compliant standards: IEC60898-1 • Rated current: 1A,2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A • Rated voltage: 240/415V • Frequency: 50/60Hz • Electromagnetic release type: B, C, D • Number of poles: 1P, 1P+N, 2P, 3P, 3P+N, 4P
• Mechanical life: 20000 cycles • Electrical life: 10000 cycles • Rated short-circuit breaking capacity(Icu): 10000A
NXB-63H
• Short-circuit breaking capacity(Ics): 7500A • Rated impulse withstand voltage(Uimp): 4kV • Protection of circuits against short-circuit currents, overload currents, switch, isolation
2. TECHNICAL DATA
2. TECHNICAL DATA
Standard
IEC 60947-2
Rated current In Rated voltage Ue Rated frequency
A
1、2、3、4、6、10、16、20、25、32、40、50、63
007
008
V
230 / 400
Hz
50
Poles
1P, 1P+N, 2P, 3P, 3P+N, 4P
NB8-63
NB8-63H
Thermo-magnetic release characteristic
B(3-5In),C(5-10In),D(10-16In),
Mechanical life
20,000 10,000 10,000
Electrical life Rated breaking capacity
1. General
1. General
A V
Insulation voltage Ui
500
1.1 Function protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation. NB8 -63 circuit-breakers are used in domestic installation, as well as in commercial and industry electrical distribution systems. 1.2 Selection Technical data of the network at the point considered: short-circuit current at the circuit- breaker installation point, which must always be less than the breaking capacity of this device, network normal voltage. Tripping curves: B curve (3-5In) protection for people and big length cables in TN and IT systems. C curve (5-10In) protection for resistive and inductive loads with low inrush current. D curve(10-16In) protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps). 1.3 Certificate CE
1.1 Function Protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation. NB8 -63H circuit-breakers are used in domestic installation, as well as in commercial and industry electrical distribution systems. 1.2 Selection Technical data of the network at the point considered: short-circuit current at the circuit- breaker installation point, which must always be less than the breaking capacity of this device, network normal voltage. Tripping curves: B curve (3-5In) protection for people and big length cables in TN and IT systems. C curve (5-10In) protection for resistive and inductive loads with low inrush current. D curve(10-16In) protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps). 1.3 Certificate CE KV 6
Rated impulse withstand voltage (1.2/50) Uimp
NB8-63
NB8-63H
2. Technical features
2. Technical features
Standard
IEC 60898-1
Standard
IEC 60947-2
Rated current In Rated voltage Ue Rated frequency
A 1 、 2 、 3 、 4 、 6 、 10 、 16 、 20 、 25 、 32 、 40 、 50 、 63
Rated current In Rated voltage Ue Rated frequency
A 1 、 2 、 3 、 4 、 6 、 10 、 16 、 20 、 25 、 32 、 40 、 50 、 63
V 230/400
V 230/400
Hz 50
Hz 50
Poles
1P, 1P+N, 2P, 3P, 3P+N, 4P B(3-5In), C(5-10In), D(10-16In)
Poles
1P, 1P+N, 2P, 3P, 3P+N, 4P B(3-5In), C(5-10In), D(10-16In)
Thermo-magnetic release characteristic
Thermo-magnetic release characteristic
Mechanical life
20,000 10,000
Mechanical life
20,000 10,000
Electrical life
Electrical life
Rated breaking capacity Insulation voltage Ui
A 6000
Rated breaking capacity Insulation voltage Ui
A 10,000
V 500 Rated impulse withstand voltage (1.2/50) Uimp KV 6
V 500 Rated impulse withstand voltage (1.2/50) Uimp KV 6
3. Curve
3. Curve
t(S)
t(S)
t(S)
(S)
B curve (3~5In)
C curve (5~10In)
D curve (10~16In)
CHINT
02
CHINT
02
009
010
NB8-63M
NB8-40J
1. General
1. General
1.1 Function protection of circuits against short-circuit currents, switch, isolation. NB8 -63M circuit-breakers are used in domestic installation, as well as in commercial and industry electrical distribution systems. 1.2 Selection Technical data of the network at the point considered: short-circuit current at the circuit- breaker installation point, which must always be less than the breaking capacity of this device, network normal voltage. Tripping curves: C curve (6.4In-9.6In) protection for resistive and inductive loads with low inrush current. D curve(9.6-14.4In) protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps). 1.3 Certificate CE
1.1 Function Protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation. NB8 -40J circuit-breakers are used in domestic installation, as well as in commercial and industry electrical distribution systems. 1.2 Selection Technical data of the network at the point considered: short-circuit current at the circuit- breaker installation point, which must always be less than the breaking capacity of this device, network normal voltage. Tripping curves: B curve (3-5In) protection for people and big length cables in TN and IT systems. C curve (5-10In) protection for resistive and inductive loads with low inrush current. D curve(10-16In) protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps) 1.3 Certificate CE Miniature Circuit Breaker
NB8-63M
NB8-40J
NB8 -40J
2. TECHNICAL DATA
2. Technical features
2. Technical features
Standard
IEC 60947-2
Standard
IEC 60898-1
Rated current In Rated voltage Ue Rated frequency
A 1 、 2 、 3 、 4 、 6 、 10 、 16 、 20 、 25 、 32 、 40 、 50 、 63
Rated current In Rated voltage Ue Rated frequency
A 1 、 2 、 3 、 4 、 6 、 10 、 16 、 20 、 25 、 32 、 40 、
V 230/400
V 230/400
Hz 50
Hz 50
Poles
1P, 2P, 3P, 4P
Poles
1P, 2P, 3P, 4P
Thermo-magnetic release characteristic
C(6.4-9.6In), D(9.6-14.4In)
Thermo-magnetic release characteristic
B(3-5In), C(5-10In), D(10-16In)
Mechanical life
20,000 10,000
Mechanical life
15,000 10,000
Electrical life
Electrical life
Rated breaking capacity Insulation voltage Ui
A 10,000
Rated breaking capacity Insulation voltage Ui
A 4500(D), 6000(B, C)
V 500 Rated impulse withstand voltage (1.2/50) Uimp KV 6
V 500 Rated impulse withstand voltage (1.2/50) Uimp KV 4
3. Curve
3. Curve
C curve(5~10In)
D curve(10~16In)
011
012
NB1-63DC
CB-60
1. General
• Compliant standards: IEC/EN 60898-2, IEC/EN60898-1, EN60947-2 • Rated current: 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A • Rated voltage: DC60/110(1P),DC80/125/220(2P) • Electromagnetic release type: B, C • Number of poles: 1P, 2P
• Excellent breaking capacity • Double connection function of lead wire and bus bar • Stored energy operation, fast closing, long service life • Convenient installation, disassembly • Contact on-off indication, higher security • Green environmental protection and energy saving
• Mechanical life: 20000 cycles • Electrical life: 10000 cycles • Rated short-circuit breaking capacity(Icn): 6kA
2. Technical features
Standard
IEC/EN 60898-1
CB-60
NB1-63DC
Rated current In
A 1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63
Poles
1P, 2P, 3P, 4P
Rated voltage Ue
V
230/400
Electrical life
4,000
Mechanical life
20,000
CB-125
3. Curve
• Compliant standards: EN60947-2 • Rated current: 63A, 80A, 100A, 125A • Rated voltage: DC60/110(1P),DC80/125/220(2P) • Number of poles: 1P, 2P • Mechanical life: 20000 cycles • Electrical life: 8000 cycles • Rated short-circuit breaking capacity(IcU): 20kA
C curve
t(s) 10000 5000 1H
2000 1000
500 200 100
50 20 10
CB-125
5 2 1
0.5 0.2 0.1
0.05 0.02 0.01
0.005 0.002 0.001 0.5 1 23 45 7 10 20 30 50 70 100 200
I/In
Low-voltage Brief Catalogue
Low-voltage Brief Catalogue
MCCB
MCCB
013
014
P -
P -
DZ158
NXB-125
1. General
• Compliant standards: IEC/EN60947-2 • Rated current: 63A, 80A, 100A(1P, 2P, 3P, 4P), 125A(1P, 2P) • Rated voltage: 230V ~ (1P), 400V ~ (2P, 3P, 4P) • Frequency: 50/60Hz • Electromagnetic release type:C: 8In, D:12In • Number of poles: 1P, 2P, 3P, 4P • Mechanical life: 20000 cycles • Electrical life: 6000 cycles (In ≤ 100A); 4000 cycles (In>100A) • Rated short-circuit breaking capacity(Icu): 10kA
• Short circuit protection • Overload protection • Switch • Isolation • Contact position indicator
NXB-125
2. Technical features
• Short-circuit breaking capacity(Ics): 7.5kA • Rated impulse withstand voltage(Uimp): 4kV
Standard
IEC/EN 60947-2
DZ158
Rated current In
A 63 、 80 、 100 、 125
Poles
1P, 2P, 3P, 4P
Rated voltage Ue Rated frequency
V 230/400~240/415
Hz 50
Rated breaking capacity
kA 6/10 V 4000
Rated impulse withstand voltage (1.2/50) Uimp Thermo-magnetic release characteristic
(8-12)In
Electrical life
1,500(In=63A, 80A, 100A) 1,000(In=125A) 8,500(In=63A, 80A, 100A) 7,000(In=125A) On DIN rail EN 60715 (35mm) by means of fast clip device
Mechanical life
Mounting
Connection
From top and bottom
3. Curve
t(s) 10000 8000 1h (or 2h)
2000 1000
500 200 100
50 30 20
10 5 2 1
0.5 0.2
0.1 0.05 0.02 0.01
0.005 0.002 0.001
0.51 1.3 24 58 32
12
03 05 07 0 100
I/In
� Protection against short circuit � Contact position indicator
2. Technical features
NB310L (2P)
Low-voltage Brief Catalogue
Low-voltage Brief Catalogue
RCCB
RCCB
015
016
P -
P -
IEC/EN 61009-1
Standard Type (wave form of the earth leakage sensed)
A, AC
A
NL1
NL210 Residual Current Operated Circuit Breaker without over-current protection B, C Thermo-magnetic release characteristic Poles 2P 3PN
6-40 3P+N 400
A
6-32 2P
Rated current In Poles
1. General
1. General Rated voltage Ue Rated sensitivity I △ n Rated short-circuit capacity lcn Break time under I △ n Electrical life Mechanical life
230/240
A V A s
1.1 Function Protect people against indirect contacts and additional protection against direct contacts. Protect installations against fire hazard due to insulation faults. Residual current circuit breakers are used in housing, tertiary sector and industry. 1.2 Detectable wave form AC class Tripping is ensured for slowly increasing sinusoidal AC residual currents. A class Tripping is ensured for sinusoidal AC residual currents and for pulsed DC residual currents, whether applied suddenly or increasing slowly. S, G/SI class Tripping is ensured not only for sinusoidal AC residual currents but also for pulsed DC residual currents whether applied suddenly or increasing slowly. S, G/SI type with filters against spurious tripping caused by harmonics and transient surges. 1.3 Tripping sensitivity 10mA - precision instrument leakage protection and bathroom use. 30mA - additional protection against direct contact. 100mA - co-ordinated with the earth system according to the formula IΔn < 50/R, to provide protection against indirect contacts; 300mA/500mA - protection against indirect contacts, as well as fire hazard. Tripping time Instantaneous It ensures instantaneous tripping (without time-delay). Short time delay It ensures any tripping at least 10ms. Selective It ensures total discrimination with a nonselective RCD placed downstream With the impact of 8/20us surge 3000A, this high immunity RCCB will still be in stable status.
0.03
• Protect people against indirect contacts and additional protection against direct contacts. • Protect installations against fire hazard due to insulation faults. 6,000 ≤ 0.1
2,000 2,000
10000
2. Detectable wave form
On DIN rail EN 60715 (35mm) by means of fast clip device From top and bottom
Mounting
NL1
• B Class Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.
Connection
3. Curve
NB310L (3PN)
B, C curve
3. Tripping sensitivity
t(s) 10000 5000 1h 2000 1000
30mA-additional protection against direct contact.
B
500 200 100
4. Tripping time
50 20 10
• Instantaneous It ensures instantaneous tripping (without time-delay).
NL1
C
5 2 1
0.5 0.2 0.1
5. Fault current indicator
NL210
0.05 0.02 0.01
6. Technical features
0.005 0.002 0.001
Standard
IEC/EN 61008-1
0.5 1
2 34 5 7 10 20 30 5070100 200 I/In
Type (wave form of the earth leakage sensed)
B
Rated current In
A 25, 40, 63
Poles
4P
Rated voltage Ue
V 400
Rated sensitivity I △ n
A 0.03
2. Technical features
Short-circuit current Icn=I △ c
A 10000
Electrical life
2,000
IEC/EN 62423 & IEC/EN 61008-1
Standard
IEC/EN 61008-1
Mechanical life
10000
Type (wave form of the earth leakage sensed)
AC, A
AC-G, A-G, A-SI
AC, A
AC-S, A-S
F
Terminal connection type
Cable/U-type busbar/Pin-type busbar
Rated current In
A 25, 40, 63
25, 40, 63
80, 100
63, 80, 100
25, 40, 63
Mounting
On DIN rail EN 60715 (35mm) by means of fast clip device
Poles
1P+N, 3P+N
Rated voltage Ue
V
230/400~240/415 0.01for1P+N 25A, 0.03, 0.1, 0.3, 0.5
Connection
From top and Bottom
Rated sensitivity I △ n
A
0.03, 0.1, 0.3 0.03, 0.1, 0.3 0.1, 0.3
0.03, 0.1, 0.3
Insulation voltage Ui
V 500
500 (In=25A/40A) 500 (In=25A/40A) 1000
500 (In=25A/40A)
Rated residual making and breaking capacity I △ m
1000 (In=63A/80A/100A)
Electrical features
A
(In=80A/100A)
630 (In=63A) 6000/10000
630 (In=63A)
630 (In=63A)
Short-circuit current Inc=I △ c
A A
10000
SCPD fuse
10000
Break time under I △ n
s ≤0.1(Normal type), 10ms~300ms(G type). 150ms~500ms(S type)
Rated frequency
Hz 50/60
Rated impulse withstand voltage(1.2/50) Uimp V 6000 Dielectric test voltage at ind. Freq. for 1 min kV 2 Pollution degree 2
018 Low-voltage Brief Catalogue NB1L Residual Current Operated Circuit Breaker with Over-current Protection (Magnetic) RCBO P - 1. General NB1L Residual Current Operated Circuit Breaker with Over-current Protection (Magnetic) ▪ Protection against risk of fire ▪ Protection against risk of electric shock
Low-voltage Brief Catalogue
RCCB
017
P -
NXL-63
1. General
▪ Protection against overload ▪ Protection against short circuit ▪ Contact position indicator 1. General
1.1 Function
Control electric circuits. Protect people against indirect contacts and additional protection against direct contacts. Protect installations against fire hazard due to insulation faults. Residual current circuit breakers are used in housing, tertiary sector and industry. 1.2 Selection Detectable wave form AC class Tripping is ensured for slowly increasing sinusoidal AC residual currents. A class Tripping is ensured for sinusoidal AC residual currents and for pulsed DC residual currents, whether applied suddenly or increasing slowly. Tripping sensitivity 10mA - precision instrument leakage protection and bathroom use. 30mA - additional protection against direct contact. 300mA - protection against indirect contacts, as well as fire hazard. Tripping time Instantaneous It ensures instantaneous tripping (without time-delay)
• Protection against risk of fire • Protection against risk of electric shock
2. Technical features
• Protection against overload • Protection against short circuit • Contact position indicator
NB1L
IEC/EN 61009-1
Standard Type (wave form of the earth leakage sensed) Thermo-magnetic release characteristic 2. Technical features
AC, A
NXL-63
NB1L
B, C
1, 2, 3, 4, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63 1~25/6~40 1P+N, 2P, 3P, 3P+N, 4P
MCB+add-on RCCB block Combined MCB+add-on RCCB block Combined IEC/EN 61009-1 AC, A B, C
Rated current In Standard
A
Type (wave form of the earth leakage sensed)
Poles
Thermo-magnetic release characteristic
1P+N, 2P
1, 2, 3, 4, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63
Rated voltage Ue Rated sensitivity I △ n Rated short-circuit capacity lcn Break time under I △ n Electrical life Mechanical life Rated current In Poles Rated voltage Ue
230/400~240/415 MCB+add-on RCCB block
A V A s
A
6,000/10,000 ≤0.1 0.03, 0.1, 0.3
Combined
1~25/6~40
MCB+add-on RCCB block 1P+N, 2P, 3P, 3P+N, 4P Combined 1P+N, 2P
2,000 2,000
V
230/400~240/415
NXL-63
2. Technical features
On DIN rail EN 60715 (35mm) by means of fast clip device From top and bottom (for combined type) From top (MCB+add-on RCCB block) 6,000/10,000 ≤0.1
Rated sensitivity I △ n
A 0.03, 0.1, 0.3
Mounting
Rated short-circuit capacity lcn
A
Standard
IEC/EN 61008-1
Connection
Break time under I △ n
s
Type (wave form of the earth leakage sensed)
AC, A
Electrical life
2,000
Rated current In
A 16, 25, 32, 40, 63
Mechanical life
2,000
3. Curve
Poles
1P+N, 3P+N
B, C curve On DIN rail EN 60715 (35mm) by means of fast clip device
Rated voltage Ue
V
230/400~240/415, 110/200~127/220
Mounting
Rated sensitivity I △ n Insulation voltage Ui
A 0.01(Only for 1P+N 16A, 25A), 0.03, 0.3
t(s) 10000 5000 1h 2000 1000
From top and bottom (for combined type) From top (MCB+add-on RCCB block)
V 500
Connection
From top and Bottom 500 (In=16A/25A/32A/40A) 630 (In=63A)
Rated residual making and breaking capacity I △ m
A
Electrical features
B
500 200 100
Short-circuit current Inc=I △ c
A A
6000/10000
3. Curve
SCPD fuse
10000
50 20 10
B, C, curve
Break time under I △ n
s
≤0.1
Rated frequency
Hz 50/60
C
5 2 1
Rated impulse withstand voltage(1.2/50) Uimp V 6000 Dielectric test voltage at ind. Freq. for 1 min kV 2 Pollution degree 2
t(s) 10000 5000 1h 2000 1000
0.5 0.2 0.1
Electrical life
2,000 2,000
0.05 0.02 0.01
B
500 200 100
Mechanical life
Fault current indicator
Yes
Mechanical features
0.005 0.002 0.001
50 20
Protection degree
IP20
0.5 1
2 34 5 7 10 20 30 5070100 200 I/In
Ambient temperature (with daily average≤35 ℃ ) ℃
-5...+40 -25...+70
10 5 2 1
C
Storage temperation
℃
0.5 0.2
0.1 0.05 0.02 0.01
0.005 0.002 0.001
2 34 5 71 02 0 30 5070100 200 I/In
0.51
020 NB310L Residual Current Operated Circuit Breaker with Over-current Protection (Magnetic) Low-voltage Brief Catalogue RCBO P - 1. General NB310L Residual Current Operated Circuit Breaker with Over-current Protection (Magnetic)
Low-voltage Brief Catalogue
RCBO
019
P -
NB1L-40/63
� Protection against risk of fire � Protection against risk of electric shock � Protection against overload � Protection against short circuit � Contact position indicator • Protection against risk of fire • Protection against risk of electric shock 1. General
1. General
• Protection against risk of fire • Protection against risk of electric shock
• Protection against overload • Protection against short circuit • Contact position indicator
2. Technical features
• Protection against overload • Protection against short circuit • Contact position indicator
NB310L (2P)
IEC/EN 61009-1
Standard Type (wave form of the earth leakage sensed)
2. Technical features
A, AC
A
Thermo-magnetic release characteristic 2. Technical features Poles
3PN
2P
Standard
IEC/EN 61009-1
B, C
NB1L-40/63
NB310L (2P)
Type (wave form of the earth leakage sensed)
AC, A for NB1L-40; AC for NB1L-63
6-40 3P+N 400 A, AC
A
6-32 2P
Rated current In Poles Standard
IEC/EN 61009-1
Thermo-magnetic release characteristic
B, C
Type (wave form of the earth leakage sensed)
A
Rated voltage Ue Rated sensitivity I △ n Rated short-circuit capacity lcn Break time under I △ n Electrical life Mechanical life Poles Rated current In
230/240
A V A s
1, 2, 3, 4, 6, 8, 10, 13, 16, 20, 25, 32, 40
NB1L-40
0.03 2P
Rated current In
A
3PN
NB1L-63
50, 63
6,000 ≤ 0.1 2,000 2,000 B, C 2P
Thermo-magnetic release characteristic
Poles
NB1L-40/NB1L-63
1P+N, 2P, 3P, 3P+N, 4P
A 6-32
6-40
Rated voltage Ue
V
230/400~240/415
10000 3P+N
Poles
Rated sensitivity I △ n
A 0.03, 0.1, 0.3
On DIN rail EN 60715 (35mm) by means of fast clip device From top and bottom 230/240
Mounting
Rated voltage Ue
V
400
Rated residual making and breaking capacity I △ m A
500 (In≤40A) 630 (In>40A)
Connection
Rated sensitivity I △ n
A 0.03
Rated short-circuit capacity lcn
A
6,000/10,000
Rated short-circuit capacity lcn
A 6,000
3. Curve
Break time under I △ n
s
≤0.1
Break time under I △ n
s
≤0.01
NB310L (3PN)
B, C curve
Rated frequency Hz 50/60 Rated impulse withstand voltage(1.2/50) Uimp V 6,000 Dielectric test voltage at ind. Freq. for 1 min kV 2 Insulation voltage Ui 500 Protection degree 2 Electrical life 2,000 Mechanical life 20,000
Electrical life
2,000
t(s) 10000 5000 1h 2000 1000
Mechanical life
2,000
10000
Mounting
On DIN rail EN 60715 (35mm) by means of fast clip device
B
500 200 100
Connection
From top and bottom
NB310L (3PN)
50 20 10
C
3. Curve
5 2 1
B, C, curve
0.5 0.2 0.1
t(s) 10000 5000 1h 2000 1000
0.05 0.02 0.01
0.005 0.002 0.001
B
500 200 100
0.5 1
2 34 5 7 10 20 30 5070100 200 I/In
50 20
10 5 2 1
C
0.5 0.2
0.1 0.05 0.02 0.01
0.005 0.002 0.001
2 34 5 71 02 0 30 5070100 200 I/In
0.51
Low-voltage Brief Catalogue
Low-voltage Brief Catalogue
RCBO
RCBO
021
022
P -
P -
NB2LE Residual Current Operated Circuit Breaker
NB3LE Residual Current Operated Circuit Breaker with Over-current Protection (Electronic)
1. General
1. General
• Protection against risk of fire • Protection against risk of electric shock
• Protection against risk of fire • Protection against risk of electric shock
• Protection against overload • Protection against short circuit
• Protection against overload • Protection against short circuit • 1P+N in one module • Contact position indicator
2. Technical features
2. Technical features
Standard
IEC/EN 61009-1
Type (wave form of the earth leakage sensed)
AC, A
Standard
IEC/EN 61009-1
NB2LE
NB3LE
Thermo-magnetic release characteristic
B, C
Type (wave form of the earth leakage sensed)
AC, A
Thermo-magnetic release characteristic
B, C
Rated current In
A 6, 10, 16, 20, 25, 32, 40
Rated current In
A 6, 10, 16, 20, 25, 32
Poles
1P+N
Poles
1P+N
Rated voltage Ue
V 240
Rated voltage Ue
V 240
Rated sensitivity I △ n
A 0.03
Rated sensitivity I △ n
A 0.03
Short-circuit current Icn
A 6000
Short-circuit current Icn
A 6,000
Break time under I △ n
s
≤0.1
Electrical life
2,000
Electrical life
2,000
Mechanical life
1,000
Mechanical life
2,000
Mounting
On DIN rail EN 60715 (35mm) by means of fast clip device
Terminal connection type
Cable/U-type busbar/Pin-type busbar
Connection
From top and bottom
Mounting
On DIN rail EN 60715 (35mm) by means of fast clip device
Connection
From top
3. Curve
3. Curve
B, C curve
B, C, curve
t(s) 10000 5000 1h 2000 1000
t (s) 10000 5000 1h 2000 1000
B
B
500 200 100
500 200 100
50 20
50 20
10 5 2 1
10 5 2
C
C
1
0.5 0.2
0,5 0,2
0.1 0.05 0.02 0.01
0,1
0,05 0,02
0,01
0.005 0.002 0.001
0,005 0,002
0,001
2 34 5 71 02 0 30 5070100 200 I/In
0.51
0,51
23 45 71 02 0 30 50 70 100 200
I/In
Low-voltage Brief Catalogue
Low-voltage Brief Catalogue
RCBO
RCBO
023
024
P -
P -
NB3LEU Residual Current Operated Circuit Breaker with Over-current Protection (Electronic)
NB3LEG - 40 Residual Current Operated Circuit Breaker with Over-current Protection (Electronic)
1. General
1. General
• Protection against risk of fire • Protection against risk of electric shock
• Protection against risk of fire • Protection against risk of electric shock
• Protection against overload • Protection against short circuit • 1P+N in one module • Contact position indicator
• Protection against overload • Protection against short circuit • 1P+N in one module • Contact position indicator
2. Technical features
2. Technical features
NB3LEU
NB3LEG-40
Standard
IEC/EN 61009-1
Standard
IEC/EN 61009-1
Type (wave form of the earth leakage sensed)
AC, A
Type (wave form of the earth leakage sensed)
AC, A
Thermo-magnetic release characteristic
B, C
Thermo-magnetic release characteristic
B, C
Rated current In
A 6, 10, 13, 16, 20, 25, 32, 40, 45, 50
Rated current In
A 6, 10, 13, 16, 20, 25, 32, 40
Poles
1P+N
Poles
1P+N
Rated voltage Ue
V 240
Rated voltage Ue
V 230-240
Rated sensitivity I △ n
A 0.03
Rated sensitivity I △ n
A 0.01, 0.03
Short-circuit current Icn
A 10,000
Short-circuit current Icn
A 6000
Break time under I △ n
s
≤0.1
Break time under I △ n
s
≤0.1
Electrical life
2,000
Electrical life
2,000
Mechanical life
2,000
Mechanical life
2,000
Terminal connection type
Cable/U-type busbar/Pin-type busbar
Terminal connection type
Cable/U-type busbar/Pin-type busbar
Mounting
On DIN rail EN 60715 (35mm) by means of fast clip device
Mounting
On DIN rail EN 60715 (35mm) by means of fast clip device
Connection
From bottom
Connection
From bottom
3. Curve
3. Curve
B, C curve
B, C, curve
t (s) 10000 5000 1h 2000 1000
t (s) 10000 5000 1h 2000 1000
B
B
500 200 100
500 200 100
50 20
50 20
10 5 2
C
10 5 2
C
1
1
0,5 0,2
0,5 0,2
0,1
0,1
0,05 0,02
0,05 0,02
0,01
0,01
0,005 0,002
0,005 0,002
0,001 0,5 1 2 345 71 02 0 30 5070100 200 I/In
0,001 0,5 1 2 345 71 02 0 30 5070100 200 I/In
Low-voltage Brief Catalogue
Low-voltage Brief Catalogue
RCBO
RCBO
025
026
P -
P -
NB4LE Residual Current Operated Circuit Breaker (Electronic)
NBH8LE Residual Current Operated Circuit Breaker with Over-current Protection (Electronic)
1. General
1. General
1.1 Function Personnel and fire protection: Cable and line protection against overload and short-circuits. 1.2 Selection Rated residual operating current I∆n = 30mA, additional protection in the case of direct contact. RCD Type A RCD Type A is ensured for sinusoidal, alternating residual currents as well as for pulsed DC residual currents, whether they be quickly or slowly increase. Tripping curve: B curve (3 In-5 In) protection and control of the circuits against overloads and short-circuits; protection for people and big length cables in TN and IT systems. C curve (5 In-10 In) protection and control of the circuits against overloads and short-circuits; protection for resistive and inductive loads with low inrush current.
• Protection against risk of fire • Protection against risk of electric shock
• Protection against overload • Protection against short circuit
2. Technical features
Standard
IEC/EN 61009-1
NB4LE
NBH8LE
Type (wave form of the earth leakage sensed)
AC
Thermo-magnetic release characteristic
C
2. Technical features
Rated current In
A 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40
Standard
IEC/EN 61008-1
Type (wave form of the earth leakage sensed) Thermo-magnetic release characteristic
A
Poles
1P+N
B, C
Rated voltage Ue
V
230/240
Rated current In
A 6, 10, 13, 16, 20, 25, 32
Poles
2P
Rated sensitivity I △ n
A 0.01, 0.03
Rated voltage Ue
V
230/400
Rated sensitivity I △ n
A 0.03
Short-circuit current Icn
A
4,500/6,000
Rated residual making and breaking capacity I △ m Rated short-circuit capacity lcn
A 3,000
Electrical features
Electrical life
4,000
A 6,000
Break time under I △ n
s
≤0.1
Mechanical life
20,000
Rated frequency
Hz 50/60
Rated impulse withstand voltage(1.2/50) Uimp kV 4 Dielectric test voltage at ind. Freq. for 1 min kV 2 Insulation voltage Ui V 500 Pollution degree 2
Mounting
On DIN rail EN 60715 (35mm) by means of fast clip device
Connection
From top
Electrical life
2,000
3. Curve
Mechanical life
10,000
C curve
Contact position indicator
Yes
Mechanical features
Protection degree
IP20
t(s) 10000 5000 1h 2000 1000
Ambient temperature (with daily average≤35 ℃ ) ℃
-25...+40 -25...+70
Storage temperation
℃
3. Curve
500 200 100
t(s) 10000 5000 1h 2000 1000
B curve
C curve
t(s) 10000 5000 1h 2000 1000
50 20
10 5 2
500 200 100
500 200 100
50 20 10
1
50 20 10
0.5 0.2
5 2 1
5 2 1
0.1
0.05 0.02
0.5 0.2 0.1
0.5 0.2 0.1
0.01
0.05 0.02 0.01
0.005 0.002
0.05 0.02 0.01
0.005 0.002 0.001
0.005 0.002 0.001
0.001
2 3 45 7 10 20 30 5070100200 I/In
0.5 1
0.5 1 2 3 4 5 7 10 20 30 5070100 200 1/In
0.5 1 2 3 4 5 7 10 20 30 5070 100 200 1/In
Page 1 Page 2-3 Page 4-5 Page 6-7 Page 8-9 Page 10-11 Page 12-13 Page 14 Page 15 Page 16-17 Page 18-19 Page 20-21 Page 22-23 Page 24-25 Page 26-27 Page 28-29 Page 30-31 Page 32-33 Page 34-35 Page 36-37 Page 38-39 Page 40-41 Page 42-43 Page 44-45 Page 46-47 Page 48-49 Page 50-51 Page 52-53 Page 54-55 Page 56-57 Page 58-59 Page 60-61 Page 62-63 Page 64-65 Page 66-67 Page 68-69 Page 70-71 Page 72-73 Page 74-75 Page 76-77 Page 78-79 Page 80-81 Page 82-83 Page 84-85 Page 86-87 Page 88-89 Page 90-91 Page 92-93 Page 94-95 Page 96-97 Page 98-99 Page 100-101 Page 102-103 Page 104-105 Page 106-107 Page 108-109 Page 110-111 Page 112-113 Page 114-115 Page 116-117 Page 118-119 Page 120-121 Page 122-123 Page 124-125 Page 126-127 Page 128-129 Page 130-131 Page 132-133 Page 134-135 Page 136-137 Page 138-139 Page 140-141 Page 142-143 Page 144Powered by FlippingBook