CHINT Low-voltage Brief Catalogue

2. TECHNICAL DATA

2. TECHNICAL DATA

Standard

IEC 60947-2

Rated current In Rated voltage Ue Rated frequency

A

1、2、3、4、6、10、16、20、25、32、40、50、63

007

008

V

230 / 400

Hz

50

Poles

1P, 1P+N, 2P, 3P, 3P+N, 4P

NB8-63

NB8-63H

Thermo-magnetic release characteristic

B(3-5In),C(5-10In),D(10-16In),

Mechanical life

20,000 10,000 10,000

Electrical life Rated breaking capacity

1. General

1. General

A V

Insulation voltage Ui

500

1.1 Function protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation. NB8 -63 circuit-breakers are used in domestic installation, as well as in commercial and industry electrical distribution systems. 1.2 Selection Technical data of the network at the point considered: short-circuit current at the circuit- breaker installation point, which must always be less than the breaking capacity of this device, network normal voltage. Tripping curves: B curve (3-5In) protection for people and big length cables in TN and IT systems. C curve (5-10In) protection for resistive and inductive loads with low inrush current. D curve(10-16In) protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps). 1.3 Certificate CE

1.1 Function Protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation. NB8 -63H circuit-breakers are used in domestic installation, as well as in commercial and industry electrical distribution systems. 1.2 Selection Technical data of the network at the point considered: short-circuit current at the circuit- breaker installation point, which must always be less than the breaking capacity of this device, network normal voltage. Tripping curves: B curve (3-5In) protection for people and big length cables in TN and IT systems. C curve (5-10In) protection for resistive and inductive loads with low inrush current. D curve(10-16In) protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps). 1.3 Certificate CE KV 6

Rated impulse withstand voltage (1.2/50) Uimp

NB8-63

NB8-63H

2. Technical features

2. Technical features

Standard

IEC 60898-1

Standard

IEC 60947-2

Rated current In Rated voltage Ue Rated frequency

A 1 、 2 、 3 、 4 、 6 、 10 、 16 、 20 、 25 、 32 、 40 、 50 、 63

Rated current In Rated voltage Ue Rated frequency

A 1 、 2 、 3 、 4 、 6 、 10 、 16 、 20 、 25 、 32 、 40 、 50 、 63

V 230/400

V 230/400

Hz 50

Hz 50

Poles

1P, 1P+N, 2P, 3P, 3P+N, 4P B(3-5In), C(5-10In), D(10-16In)

Poles

1P, 1P+N, 2P, 3P, 3P+N, 4P B(3-5In), C(5-10In), D(10-16In)

Thermo-magnetic release characteristic

Thermo-magnetic release characteristic

Mechanical life

20,000 10,000

Mechanical life

20,000 10,000

Electrical life

Electrical life

Rated breaking capacity Insulation voltage Ui

A 6000

Rated breaking capacity Insulation voltage Ui

A 10,000

V 500 Rated impulse withstand voltage (1.2/50) Uimp KV 6

V 500 Rated impulse withstand voltage (1.2/50) Uimp KV 6

3. Curve

3. Curve

t(S)

t(S)

t(S)

(S)

B curve (3~5In)

C curve (5~10In)

D curve (10~16In)