CHINT Low-voltage Brief Catalogue

009

010

NB8-63M

NB8-40J

1. General

1. General

1.1 Function protection of circuits against short-circuit currents, switch, isolation. NB8 -63M circuit-breakers are used in domestic installation, as well as in commercial and industry electrical distribution systems. 1.2 Selection Technical data of the network at the point considered: short-circuit current at the circuit- breaker installation point, which must always be less than the breaking capacity of this device, network normal voltage. Tripping curves: C curve (6.4In-9.6In) protection for resistive and inductive loads with low inrush current. D curve(9.6-14.4In) protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps). 1.3 Certificate CE

1.1 Function Protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation. NB8 -40J circuit-breakers are used in domestic installation, as well as in commercial and industry electrical distribution systems. 1.2 Selection Technical data of the network at the point considered: short-circuit current at the circuit- breaker installation point, which must always be less than the breaking capacity of this device, network normal voltage. Tripping curves: B curve (3-5In) protection for people and big length cables in TN and IT systems. C curve (5-10In) protection for resistive and inductive loads with low inrush current. D curve(10-16In) protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps) 1.3 Certificate CE Miniature Circuit Breaker

NB8-63M

NB8-40J

NB8 -40J

2. TECHNICAL DATA

2. Technical features

2. Technical features

Standard

IEC 60947-2

Standard

IEC 60898-1

Rated current In Rated voltage Ue Rated frequency

A 1 、 2 、 3 、 4 、 6 、 10 、 16 、 20 、 25 、 32 、 40 、 50 、 63

Rated current In Rated voltage Ue Rated frequency

A 1 、 2 、 3 、 4 、 6 、 10 、 16 、 20 、 25 、 32 、 40 、

V 230/400

V 230/400

Hz 50

Hz 50

Poles

1P, 2P, 3P, 4P

Poles

1P, 2P, 3P, 4P

Thermo-magnetic release characteristic

C(6.4-9.6In), D(9.6-14.4In)

Thermo-magnetic release characteristic

B(3-5In), C(5-10In), D(10-16In)

Mechanical life

20,000 10,000

Mechanical life

15,000 10,000

Electrical life

Electrical life

Rated breaking capacity Insulation voltage Ui

A 10,000

Rated breaking capacity Insulation voltage Ui

A 4500(D), 6000(B, C)

V 500 Rated impulse withstand voltage (1.2/50) Uimp KV 6

V 500 Rated impulse withstand voltage (1.2/50) Uimp KV 4

3. Curve

3. Curve

C curve(5~10In)

D curve(10~16In)

Powered by