CHINT Low-voltage Brief Catalogue

� Protection against short circuit � Contact position indicator

2. Technical features

NB310L (2P)

Low-voltage Brief Catalogue

Low-voltage Brief Catalogue

RCCB

RCCB

015

016

P -

P -

IEC/EN 61009-1

Standard Type (wave form of the earth leakage sensed)

A, AC

A

NL1

NL210 Residual Current Operated Circuit Breaker without over-current protection B, C Thermo-magnetic release characteristic Poles 2P 3PN

6-40 3P+N 400

A

6-32 2P

Rated current In Poles

1. General

1. General Rated voltage Ue Rated sensitivity I △ n Rated short-circuit capacity lcn Break time under I △ n Electrical life Mechanical life

230/240

A V A s

1.1 Function Protect people against indirect contacts and additional protection against direct contacts. Protect installations against fire hazard due to insulation faults. Residual current circuit breakers are used in housing, tertiary sector and industry. 1.2 Detectable wave form AC class Tripping is ensured for slowly increasing sinusoidal AC residual currents. A class Tripping is ensured for sinusoidal AC residual currents and for pulsed DC residual currents, whether applied suddenly or increasing slowly. S, G/SI class Tripping is ensured not only for sinusoidal AC residual currents but also for pulsed DC residual currents whether applied suddenly or increasing slowly. S, G/SI type with filters against spurious tripping caused by harmonics and transient surges. 1.3 Tripping sensitivity 10mA - precision instrument leakage protection and bathroom use. 30mA - additional protection against direct contact. 100mA - co-ordinated with the earth system according to the formula IΔn < 50/R, to provide protection against indirect contacts; 300mA/500mA - protection against indirect contacts, as well as fire hazard. Tripping time Instantaneous It ensures instantaneous tripping (without time-delay). Short time delay It ensures any tripping at least 10ms. Selective It ensures total discrimination with a nonselective RCD placed downstream With the impact of 8/20us surge 3000A, this high immunity RCCB will still be in stable status.

0.03

• Protect people against indirect contacts and additional protection against direct contacts. • Protect installations against fire hazard due to insulation faults. 6,000 ≤ 0.1

2,000 2,000

10000

2. Detectable wave form

On DIN rail EN 60715 (35mm) by means of fast clip device From top and bottom

Mounting

NL1

• B Class Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.

Connection

3. Curve

NB310L (3PN)

B, C curve

3. Tripping sensitivity

t(s) 10000 5000 1h 2000 1000

30mA-additional protection against direct contact.

B

500 200 100

4. Tripping time

50 20 10

• Instantaneous It ensures instantaneous tripping (without time-delay).

NL1

C

5 2 1

0.5 0.2 0.1

5. Fault current indicator

NL210

0.05 0.02 0.01

6. Technical features

0.005 0.002 0.001

Standard

IEC/EN 61008-1

0.5 1

2 34 5 7 10 20 30 5070100 200 I/In

Type (wave form of the earth leakage sensed)

B

Rated current In

A 25, 40, 63

Poles

4P

Rated voltage Ue

V 400

Rated sensitivity I △ n

A 0.03

2. Technical features

Short-circuit current Icn=I △ c

A 10000

Electrical life

2,000

IEC/EN 62423 & IEC/EN 61008-1

Standard

IEC/EN 61008-1

Mechanical life

10000

Type (wave form of the earth leakage sensed)

AC, A

AC-G, A-G, A-SI

AC, A

AC-S, A-S

F

Terminal connection type

Cable/U-type busbar/Pin-type busbar

Rated current In

A 25, 40, 63

25, 40, 63

80, 100

63, 80, 100

25, 40, 63

Mounting

On DIN rail EN 60715 (35mm) by means of fast clip device

Poles

1P+N, 3P+N

Rated voltage Ue

V

230/400~240/415 0.01for1P+N 25A, 0.03, 0.1, 0.3, 0.5

Connection

From top and Bottom

Rated sensitivity I △ n

A

0.03, 0.1, 0.3 0.03, 0.1, 0.3 0.1, 0.3

0.03, 0.1, 0.3

Insulation voltage Ui

V 500

500 (In=25A/40A) 500 (In=25A/40A) 1000

500 (In=25A/40A)

Rated residual making and breaking capacity I △ m

1000 (In=63A/80A/100A)

Electrical features

A

(In=80A/100A)

630 (In=63A) 6000/10000

630 (In=63A)

630 (In=63A)

Short-circuit current Inc=I △ c

A A

10000

SCPD fuse

10000

Break time under I △ n

s ≤0.1(Normal type), 10ms~300ms(G type). 150ms~500ms(S type)

Rated frequency

Hz 50/60

Rated impulse withstand voltage(1.2/50) Uimp V 6000 Dielectric test voltage at ind. Freq. for 1 min kV 2 Pollution degree 2

Powered by