Low-voltage Brief Catalogue
Low-voltage Brief Catalogue
Modular Din Rail Product
Modular Din Rail Product
029
030
P -
P -
NXBLE-32
NXBLE-63Y
• Compliant standards: IEC61009-1 • Rated current: 6A, 10A, 16A, 20A, 25A, 32A • Rated residual operating current: 0.03A, 0.05A, 0.075A, 0.1A, 0.3A • Rated voltage: 240V~(1P+N, 2P), 415V~(3P, 3P+N, 4P) • Frequency: 50/60Hz • Electromagnetic release type: B, C, D • Number of poles: 1P+N, 2P, 3P, 3P+N, 4P
• Compliant standards: IEC61009-1 • Rated current: 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A • Rated residual operating current: 0.01A, 0.03A • Rated voltage: 240V/415V • Frequency: 50/60Hz • Electromagnetic release type: C, D • Number of poles: 1P+N
• Mechanical life: 20000 cycles • Electrical life: 10000 cycles • Rated short-circuit breaking capacity(Icu): 6000A • Short-circuit breaking capacity(Ics): 6000A • Rated impulse withstand voltage(Uimp): 4kV
• Mechanical life: 20000 cycles • Electrical life: 10000 cycles • Rated short-circuit breaking capacity(Icu): 4500A • Short-circuit breaking capacity(Ics): 4500A • Rated impulse withstand voltage(Uimp): 4kV
NXBLE-32
NXBLE-63Y
NXBLE-40
NXBLE-125
• Compliant standards: IEC61009-1 • Rated current: 6A, 10A, 16A, 20A, 25A, 32A, 40A • Rated residual operating current: 0.01A, 0.03A • Rated voltage: 240/415V • Frequency: 50/60Hz • Electromagnetic release type: C, D • Number of poles: 1P+N • Mechanical life: 20000 cycles • Electrical life: 10000 cycles • Rated short-circuit breaking capacity(Icu): 4500A • Short-circuit breaking capacity(Ics): 4500A • Rated impulse withstand voltage(Uimp): 4kV
• Compliant standards: IEC60947-2 • Rated current: 63A, 80A, 100A, 125A • Rated residual operating current: 0.03A, 0.05A, 0.075A, 0.1A, 0.3A • Rated voltage: 240~(1P+N, 2P), 415V~(3P, 3P+N, 4P) • Frequency: 50/60Hz • Electromagnetic release type: C, D • Number of poles: 1P+N, 2P, 3P, 3P+N, 4P • Mechanical life: 20000 cycles • Electrical life: 6000 cycles (In≤100A); 4000 cycles (In>100A) • Rated short-circuit breaking capacity(Icu): 10000A
NXBLE-40
NXBLE-125
• Short-circuit breaking capacity(Ics): 7500A • Rated impulse withstand voltage(Uimp): 4kV
NXBLE-63
NXBLE-125G
• Compliant standards: IEC61009-1 • Rated current: 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A • Rated residual operating current: 0.03A, 0.05A, 0.075A, 0.1A, 0.3A • Rated voltage: 240~(1P+N, 2P), 415V~(3P, 3P+N, 4P) • Frequency: 50/60Hz • Electromagnetic release type: B, C, D • Number of poles: 1P+N, 2P, 3P, 3P+N, 4P
• Compliant standards: IEC61009-1 • Rated current: 63A, 80A, 100A, 125A • Rated residual operating current: 0.03A, 0.05A, 0.075A, 0.1A, 0.3A • Rated voltage: 240~(1P+N, 2P), 415V~(3P, 3P+N, 4P) • Frequency: 50/60Hz • Electromagnetic release type: B, C, D • Number of poles: 1P+N, 2P, 3P, 3P+N, 4P • Mechanical life: 20000 cycles • Electrical life: 6000 cycles (In≤100A); 4000 cycles (In>100A) • Rated short-circuit breaking capacity(Icu): 10000A
• Mechanical life: 20000 cycles • Electrical life: 10000 cycles • Rated short-circuit breaking capacity(Icu): 6000A • Short-circuit breaking capacity(Ics): 6000A • Rated impulse withstand voltage(Uimp): 4kV
NXBLE-63
NXBLE-125G
• Short-circuit breaking capacity(Ics): 7500A • Rated impulse withstand voltage(Uimp): 4kV
Powered by FlippingBook