NB4LE-AFD Arc fault detection circuit-breaker with residual current operated function

NB3LE-AFD Arc fault detection circuit-breaker with residual current operated function

1. General

1. General

1.1 Function NB4LE-AFD arc fault detection circuit-breaker with residual current operated function applies to circuits with frequency of 50Hz, rated voltage AC 230/240V, and rated current up to 32A. It provides overload, short circuit, leakage protection and arc fault detection, and can also be used for infrequent switching of the circuit under normal circumstances. 1.2 Selection RCD Type Type A - Tripping is ensured for sinusoidal, alternating residualcurrents as well as for pulsed DC residual currents, whether they be quickly applied or slowly increase. Tripping curve: B curve (I1=1.13In; I2=1.45In; I4=3In; I5=5In) protection and control of the circuits against overloads and short-circuits;protection for people and big length cables in TN and IT systems. C curve (5-10 In) protection and control of the circuits against overloads and short-circuits; protection for resistive and inductive loads with low inrush current. BK curve (I1=1.05In; I2=1.3In; I4=3In; I5=5In) protection and control of the circuits against overloads and short-circuits;protection for people and big length cables in TN and IT systems. CK curve (I1=1.05In; I2=1.3In; I4=5In; I5=10In)protection and control of the circuit against overloads and short-circuits;protection for resistive and inductive loads with low inrush current.

1.1 Function NB3LE-AFD arc fault detection circuit-breaker with residual current operated function applies to circuits with frequency of 50Hz, rated voltage AC 240V, and rated current up to 32A. It provides overload, short circuit, leakage protection and arc fault detection, and can also be used for infrequent switching of the circuit under normal circumstances. 1.2 Selection RCD Type Type A - Tripping is ensured for sinusoidal, alternating residual currents as well as for pulsed DC residual currents, whether they be quickly applied or slowly increase. Tripping curve: B curve (3-5 In) protection and control of the circuits against overloads and short-circuits; protection for people and big length cables in TN and IT systems. C curve (5-10 In) protection and control of the circuits against overloads and short-circuits; protection for resistive and inductive loads with low inrush current.

NB4LE-AFD

NB3LE-AFD

2. Technical features

2. Technical features

Standard

IEC/EN61009-1,IEC/EN62606

Standard

BS-EN 61009-1,BS-EN 62606

Type (wave form of the earth leakage sensed) Thermo-magnetic release characteristic

A

Type (wave form of the earth leakage sensed) Thermo-magnetic release characteristic

A

B, C

BK, CK

B, C

Rated current In

A 6, 10, 13, 16, 20, 25, 32

10, 13, 16, 20, 25

Rated current In

A 6A, 10A, 13A, 16A, 20A, 25A, 32A

Poles

2P

Poles

1P+N

Rated voltage Ue

V

230/240

Rated voltage Ue

V

240

Rated sensitivity I △ n

A 0.03

Rated sensitivity I △ n

A 0.01, 0.03

Rated residual making and breaking capacity I △ m Rated short-circuit capacity lcn

Rated residual making and breaking capacity I △ m Rated short-circuit capacity lcn

A 3,000

A 500

Electrical features

Electrical features

A 6,000

A 6,000

Break time under I △ n

s

≤0.1 50/60

Break time under I △ n

s

≤0.1

Rated frequency

Hz

Rated frequency

Hz

50

Rated impulse withstand voltage(1.2/50) Uimp Dielectric test voltage at ind. Freq. for 1 min

kV 4 kV 2

Rated impulse withstand voltage(1.2/50) Uimp Dielectric test voltage at ind. Freq. for 1 min

V

4,000

kV 2

Insulation voltage Ui

Insulation voltage Ui

V

500

V

500

Pollution degree

2

Pollution degree

2

Electrical life

4,000

Electrical life

4,000

Mechanical life

10,000

Mechanical life

10,000

Fault indicator light Protection degree

Yes

Fault indicator light Protection degree

Yes

Mechanical features

Mechanical features

IP20

IP20

Ambient temperature (with daily average≤35 ℃ )

-25...+40 -25...+70

Ambient temperature (with daily average≤35 ℃ )

-25...+40 -25...+70

℃ ℃

℃ ℃

Storage temperation

Storage temperation

Terminal connection type

Cable/ U-type/Pin-type busbar

Terminal connection type

Cable/ U-type/Pin-type busbar

mm 2 25 AWG 18-3 10 AWG 18-8 mm 2

mm 2 16 AWG 18-5 6 AWG 18-10 mm 2

Terminal size top/bottom for cable

Terminal size top/bottom for cable

Terminal size top/bottom for busbar

Terminal size top/bottom for busbar

Installation

Installation

N·m 2 In-Ibs. 18

N·m 2 for bottom,1.2 for top In-Ibs. 18

Tightening torque

Tightening torque

Mounting

On DIN rail EN 60715 (35mm) by means of fast clip device

Mounting

On DIN rail EN 60715 (35mm) by means of fast clip device

Connection

Bottom electrical feeding

Connection

Bottom electrical feeding