CHINT Low-voltage Brief Catalogue

Low-voltage Brief Catalogue

Low-voltage Brief Catalogue

Modular Din Rail Product

Modular Din Rail Product

035

036

P -

P -

AX-X1 Auxiliary contacts 、 AL-X1 Alarm auxiliary contact

OUVT-X1 Over/under voltage release

• Rated operation voltage Ue: AC 240V, 50Hz • Overvoltage operation setting value Uvo: 280V • Rated insulation voltage Ui: 500V • Over voltage setting value: 280 (1±5%) V • Under voltage setting value : (35%~70%) Ue • Mechanical and electrical life: ≥4000 operation cycles

• Compliant standards: IEC 60947-5-1 • Rated insulation voltage (Ui): 500V • Utilization category:AC-12,DC-12 • Rated operation current under different rated operation voltage: AC-12:240V/6A,415V/3A; DC-12:130V/1A,48V/2A,24V/6A • Life time: 10000 times

AX-X1

OUVT-X1

SHT-X1 Shunt release

AX-X3 Auxiliary contacts, AL-X3 Alarm auxiliary contact

• Rated insulation voltage (Ui): 500V • Utilization category:AC-12,DC-12 • Rated operation current under different rated operation voltage: AC-12:400V/3A,230V/6A,48V/3A,24V/6A; DC-12:48V/3A,24V/6A • Action characteristics: within the range of 70% ~ 110% of the rated control supply voltage • Life time: 4000 times

• Compliant standards: IEC 60947-5-1 • Rated insulation voltage (Ui): 500V • Utilization category: AC-12, DC-12 • Rated operation current under different rated operation voltage: AC-12:240V/6A, 415V/3A; DC-12:130V/1A,48V/2A,24V/6A • Life time: 10000 times

SHT-X1

AX-X3

OVT-X1 Overvoltage release

SHT-X3 Shunt release

• Rated operation voltage Ue: AC 240V 50Hz (or 60Hz) • Rated insulation voltage Ui: 500V • Overvoltage setting value Uvo: 280V • Mechanical and electrical life: ≥4000 operation cycles

• Rated insulation voltage (Ui): 500V • Utilization category:AC-12,DC-12 • Rated operation current under different rated operation voltage: AC-12:400V/3A,230V/6A,48V/3A,24V/6A; DC-12:48V/3A,24V/6A • Action characteristics: within the range of 70% ~ 110% of the rated control supply voltage • Life time: 4000 times

OVT-X1

SHT-X3

UVT-X1 Under-voltage release

OVT-X3 Overvoltage release

• Rated operation voltage Ue: AC 240V • Rated insulation voltage Ui: 500V • Under voltage setting value: (35%~70%) Ue • Mechanical and electrical life: ≥4000 operation cycles

• Rated operation voltage Ue: AC 240V 50Hz (or 60Hz) • Rated insulation voltage Ui: 500V. • Overvoltage setting value Uvo: 280V(1±5%)V • Mechanical and electrical life: ≥4000 operation cycles

UVT-X1

OVT-X3