Surge Arrester
Pushbutton & Indicator
041
042
P -
P -
NXU-I+II
NP9 Pushbutton
1. General
1. General
For controlling electrical circuit either directly or via starters, contactors, relays etc. And pushbutton with lamp could also be used as indicator.
1.1 Compliant standards IEC/EN 61643-11 1.2 Function Protect electric system and on-loading electrical apparatus from thunder and instantaneous over-voltage. 1.3 The product is composed of two independent components removable protective module 4 and base 2. 1.4 When the product is damaged, the part 3 will indicate; please replace the removable protective module 4 at once and there is no need to cutoff the circuits. 1.5 The part 1 is for maximum continuous operational voltage indication as well as avoiding replacement with wrong module.
2. Technical features
NP9
• Manufactured according to IEC/EN 60947-5-1 • Type: Pushbutton without illuminated lamp • Electric ratings: 6A, 230V, AC50/60Hz • Electric life: 100,000 • Mechanical life: 250,000 • Type: Pushbutton with illuminated lamp • Electric ratings: 20mA, AC/DC 6.3/12/24/110/230V • Assembly of contact: 1N/C+2N/O, 2N/C+1N/O, 3N/O, 2N/C+2N/O (Not available for illuminated type) • Mounting on Din rail (TH35-7.5)
NXU-I+II
2. Technical features
Standard
IEC/EN 61643-11
Poles
1P
2P
3P
4P
1P+N
3P+N
ND9 Indicator Light
Protection mode Electrical features Class
L-PE L-N L-PE N-PE L-PE
L-PE N-PE L-N N-PE
L-N
N-PE
Ⅰ 、 Ⅱ 50/60
1. General
Frequence
Hz
Maximum continuous operational voltage Maximum impulse current (10/350μs) Iimp Nominal discharge current (8/20μs) In Maximum discharge current (8/20μs) Imax
V~ 275, 385
255
275, 385
255
Indication of signal, pre-set signal, malfunction signal etc.
kA kA kA kV
12.5
25 30 40 1.5
12.5
50 50 50
25 50
25 50
2. Technical features
Level of protection Up
1.5(for 275V), 1.8 (for 385V)
1.5(275V), 1.8(385V) 1.5
ND9
• Manufactured according to IEC/EN 60947-5-1 • Two types: single lamp & dual lamps • Electric ratings: 20mA, AC/DC 6.3/12/24/110/230V • Mounting on Din rail (TH35-7.5)
Remote indication contact (with or without) Woking indication/Fault indication
Green/Red
Green/Red
Maximum 1.5 mm 2
Maximum 1.5mm 2
Remote connection capacity
AC DC
250V/0.5A
250V/0.5A
Remote contact switch capacity
250V/0.1A; 75V/0.5A
250V/0.1A; 75V/0.5A
Installation Protection degree
IP20
Mounting Strip length Terminal size
On DIN rail EN60715(35mm) by means of fast clip device
mm 15
mm 2
16
Screw dimension Tightening torque
M5
N·m 2.0~3.0
Ambient temperature
-40~+70
℃ m
Altitude
≤2000
Relative humidity
≤95% at + 20 ℃ ; ≤50% at + 40 ℃
Mounting Environment
The place where there is no significant vibration and shock